Continuous Emission Monitoring Systems (CEMS) - Cement Plants
Continuous Emission Monitoring Systems (CEMS) - Cement Plants
Product description
CEMS for Dust, Flow, CO, NOx, SO2, CO2, O2 measurement |
|
MEASURED GASES CO - Carbon monoxide - Infrared Analyzer NOx - Nitrogen oxides - Infrared Analyzer and NO2/NO molybdenum-based converter SO2 - Sulfur dioxide - Infrared Analyzer CO2 - Carbon dioxide - Infrared Analyzer O2 - Oxygen - Extractive zirconium oxide cell Analyzer
Dust - With electro-dynamic indicator
SAMPLING AND TREATMENT SYSTEM n. 1 Probe with heated filter, n. 1 Heated line, Heated (180 °C) solenoid valves and fine filtering system, Cooler with peristaltic pump continuously operating, n. 1 Sampling pump with fast-loop tapping, Condense monitor, Flow-meters
MONITORED PLANT Cement plants
CABINET Painted plate with conditioner for temperatures up to 55 °C Degree of protection IP54
DATA PROCESSING 5 x 4-20 mA analog outputs 10 x Relay outputs for alarm and service signals
Modbus output and DAS-DAC data acquisition: remote control for service and technical support
|
|